The HS horn and Horn strobe appliance are ideal choices for retrofit applications as well as new installations. The HS/HS4 satisfy virtually all requirements for indoor, wall and ceiling mount application.
Series HS Horns and Horn Strobes
Distributed Architecture
Highly Survivable
HS Series Horn and Horn Strobes include a selectable continuous horn tone or temporal pattern (Code 3) with three selectable dBA settings for each tone. Strobe options include the Wheelock patented MCW Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount.
- HS4-24-R
- HS4-24-W
- HS4-24MCW-FR
- HS4-24MCW-FW
- HS4-121575W-FR
- HS4-24MCWH-FR
- HS4-24MCWH-FW
- HS4-24MCC-FR
- HS4-24MCC-FW
- HS4-24MCCH-FR
- HS4-24MCCH-FW
Physical Material | Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. |
Weight | HS Strobe: 0.66 lbs. (.03 kg) |
Lens | Sabic Lexan 943A |
Dimensions | HS Horn: 5.13” W x 5.13” H x 3.15”D; HS strobe: 5.13” W x 5.13” H x 5.24”D |
Operating Temperature | Indoor: 33.8°F to 120.2°F (0°C to 49°C) and maximum humidity of 93% |
Wire Connections | #12 through #18 AWG |
Power & General | |
Operating voltage | 16 – 33V (DC or FWR) |
Strobe Output Rating | UL 1971 |
Strobe Flash Rate | Strobes are designed to flash at 1 flash per second |
Synchronization Models | Strobes can be synchronized with Wheelock’s DSM Sync Modules, Power Supplies or SAFEPATH products, using Wheelock patented sync protocol |
The audible/visual notification appliance shall be Series HS4 Horn Strobe and HS Horn Appliances or approved equals. The Series HS4 and HS appliance shall meet ad be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired for Indoor Fire Protection Service) and Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirement of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The HS Horn and the audible of the HS4 appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan ® lens. The horn strobe shall be of low current design. Where wall mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for: 15/30/75/110cd or 135/185cd. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required. Where ceiling mount, multicandela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL standard 1971 for 15/30/75/95cd or 115/177cd. When synchronization is required, the appliance shall be compatible with Wheelock DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flash-rate. All notification appliances shall be backward compatible.
- About
-
HS Series Horn and Horn Strobes include a selectable continuous horn tone or temporal pattern (Code 3) with three selectable dBA settings for each tone. Strobe options include the Wheelock patented MCW Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount.
- HS4-24-R
- HS4-24-W
- HS4-24MCW-FR
- HS4-24MCW-FW
- HS4-121575W-FR
- HS4-24MCWH-FR
- HS4-24MCWH-FW
- HS4-24MCC-FR
- HS4-24MCC-FW
- HS4-24MCCH-FR
- HS4-24MCCH-FW
- Data Sheet
- Specs
-
Physical Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Weight HS Strobe: 0.66 lbs. (.03 kg) Lens Sabic Lexan 943A Dimensions HS Horn: 5.13” W x 5.13” H x 3.15”D; HS strobe: 5.13” W x 5.13” H x 5.24”D Operating Temperature Indoor: 33.8°F to 120.2°F (0°C to 49°C) and maximum humidity of 93% Wire Connections #12 through #18 AWG Power & General Operating voltage 16 – 33V (DC or FWR) Strobe Output Rating UL 1971 Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock’s DSM Sync Modules, Power Supplies or SAFEPATH products, using Wheelock patented sync protocol - Architects
-
The audible/visual notification appliance shall be Series HS4 Horn Strobe and HS Horn Appliances or approved equals. The Series HS4 and HS appliance shall meet ad be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired for Indoor Fire Protection Service) and Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirement of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The HS Horn and the audible of the HS4 appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan ® lens. The horn strobe shall be of low current design. Where wall mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for: 15/30/75/110cd or 135/185cd. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required. Where ceiling mount, multicandela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL standard 1971 for 15/30/75/95cd or 115/177cd. When synchronization is required, the appliance shall be compatible with Wheelock DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flash-rate. All notification appliances shall be backward compatible.