The XPERT 8 Base is a universal base that fits all detectors from the Soteria, Discovery and XP95 ranges.
XPERT 8 Base
Distributed Module Placement
into the XPERT 8 Intelligent Mounting Base. The base has a wide interior diameter for ease of access to cables and terminals. The ‘E-Z Fit’ feature allows you to fit the base screws, place the XPERT 8 Intelligent Mounting Base over the screws, slide it into place and tighten the screws. The detector requires a clockwise rotation into the base for fitting. Additionally the detector can be locked into the base for increased security, by a grubscrew using a 1.5mm hexagonal driver
Highly Survivable
- Wide interior diameter for ease of access to cables and terminals
- ‘E-Z Fit’ allows for simple mounting of the detector base after wiring
- Isolated and non-isolated devices supported
- Isolated wiper – maintains loop connectivity during temporary removal of devices
The XPERT 8 card, Part Number 38532-064, supplied with the base, has pre-punched pips to remove to set the address.
- SA5000-200 – XPERT 8 Intelligent Mounting Base
Part Number Specifications For PC Boards:
AC-100P-1-AAA-BBB | ||
P | Paint Option | Cabinet Color |
AAA | Module Slot 1
(lower slot) – ALM3-IP-ai |
Addressable Loop Module (ALM3-IP)
– Addressable Loops: a – IOC Circuits: i Ethernet Switch Unit |
BBB | Module Slot 2
(upper slot) – ALM3-IP-ai |
Addressable Loop Module (ALM3-IP)
– Addressable Loops: a – IOC Circuits: i |
ETP3 accommodation | An ETP3 is included if either module slot contains an ALM3-IP |
Available PC Boards:
MODEL NUMBER | DESCRIPTION |
ESU3-IP | Ethernet Switch Unit (Unmanaged 8 port) |
ALM3-IP-22 | Addressable Loop Module (2 Loops, 2 Integral Outputs) c/w APU3 |
ALM3-IP-20 | Addressable Loop Module (2 Loops, 0 Integral Outputs) c/w APU3 |
ALM3-IP-12 | Addressable Loop Module (1 Loop, 2 Integral Outputs) c/w APU3 |
ALM3-IP-10 | Addressable Loop Module (1 Loop, 0 Integral Outputs) c/w APU3 |
ALM3-IP-02 | Addressable Loop Module (0 Loops, 2 Integral Outputs) c/w APU3 |
ETP3 | Ethernet Transient Protection board (2 port) |
Part Number Specifications For Fiber Switches:
AC-100P-2-ABC-DEF | ||
P | Paint Option | Cabinet Color |
ABC-DEF | Ethernet Switch | See below |
ETP3 accommodation | Two ETP3 boards are included | |
PTP3 accommodation | A PTP3 is included |
Available Fiber Switches:
MODEL NUMBER | DESCRIPTION |
EIS6-100T-FT2 | Four-port 100BASE-TX/two-port 100BASE-FX (multimode) switch w/ST connectors |
EIS6-100T-FCS2 | Four-port 100BASE-TX/two-port 100BASE-FX (single-mode) switch w/SC connectors |
ETP3 | Two ETP3 modules are included |
PTP3 | One PTP3 module is included |
The contractor shall furnish and install, where indicated on the plans, remotely located IP-Addressable SLC and NAC circuits to distribute fire alarm system processing power, to eliminate long wiring runs back to a centrally located control panel and to increase overall system survivability. Remote SLC and NAC circuit modules shall be fully incorporated into the FxIP Fire Control system by simple CAT 5 connection. Connections shall be fully supervised, transient protected and monitored for ground faults. The combination of the IP Module and AC-100 cabinet shall be UL/ULC listed and UL/ULC listed as compatible with the Harding network fire controls. The remote cabinet shall be Harding part number AC-100 and remote IP modules shall be Harding part number(s) ALM3-IP-10, ALM3-IP-02, ALM3-IP-12, ALM3-IP-22, ALM3-IP-20, ESU3-IP, EIS6-100T-FT, EIS6-100T-FCS, ETP3, PTP3.
- About
-
The XPERT 8 card, Part Number 38532-064, supplied with the base, has pre-punched pips to remove to set the address.
- SA5000-200 – XPERT 8 Intelligent Mounting Base
- Data Sheet
- Specs
-
Part Number Specifications For PC Boards:
AC-100P-1-AAA-BBB P Paint Option Cabinet Color AAA Module Slot 1 (lower slot)
– ALM3-IP-ai
– ESU3-IPAddressable Loop Module (ALM3-IP) – Addressable Loops: a
– IOC Circuits: i
Ethernet Switch Unit
BBB Module Slot 2 (upper slot)
– ALM3-IP-ai
Addressable Loop Module (ALM3-IP) – Addressable Loops: a
– IOC Circuits: i
ETP3 accommodation An ETP3 is included if either module slot contains an ALM3-IP Available PC Boards:
MODEL NUMBER DESCRIPTION ESU3-IP Ethernet Switch Unit (Unmanaged 8 port) ALM3-IP-22 Addressable Loop Module (2 Loops, 2 Integral Outputs) c/w APU3 ALM3-IP-20 Addressable Loop Module (2 Loops, 0 Integral Outputs) c/w APU3 ALM3-IP-12 Addressable Loop Module (1 Loop, 2 Integral Outputs) c/w APU3 ALM3-IP-10 Addressable Loop Module (1 Loop, 0 Integral Outputs) c/w APU3 ALM3-IP-02 Addressable Loop Module (0 Loops, 2 Integral Outputs) c/w APU3 ETP3 Ethernet Transient Protection board (2 port) Part Number Specifications For Fiber Switches:
AC-100P-2-ABC-DEF P Paint Option Cabinet Color ABC-DEF Ethernet Switch See below ETP3 accommodation Two ETP3 boards are included PTP3 accommodation A PTP3 is included Available Fiber Switches:
MODEL NUMBER DESCRIPTION EIS6-100T-FT2 Four-port 100BASE-TX/two-port 100BASE-FX (multimode) switch w/ST connectors EIS6-100T-FCS2 Four-port 100BASE-TX/two-port 100BASE-FX (single-mode) switch w/SC connectors ETP3 Two ETP3 modules are included PTP3 One PTP3 module is included - Architects
-
The contractor shall furnish and install, where indicated on the plans, remotely located IP-Addressable SLC and NAC circuits to distribute fire alarm system processing power, to eliminate long wiring runs back to a centrally located control panel and to increase overall system survivability. Remote SLC and NAC circuit modules shall be fully incorporated into the FxIP Fire Control system by simple CAT 5 connection. Connections shall be fully supervised, transient protected and monitored for ground faults. The combination of the IP Module and AC-100 cabinet shall be UL/ULC listed and UL/ULC listed as compatible with the Harding network fire controls. The remote cabinet shall be Harding part number AC-100 and remote IP modules shall be Harding part number(s) ALM3-IP-10, ALM3-IP-02, ALM3-IP-12, ALM3-IP-22, ALM3-IP-20, ESU3-IP, EIS6-100T-FT, EIS6-100T-FCS, ETP3, PTP3.