DAPB-100 - Distributed Audio Power Booster

The DAPB-100 is a distributed audio power booster that provides an additional 100 watts of audio output power to any new or existing voice evacuation system.

Distributed Module Placement

The DAPB-100 is designed to work with any manufacturer’s voice evacuation control panel including the VECP series. Each DAPB-100 also provides an additional four Class A or Class B 25 Vrms supervised speaker circuits with an option for 70 Vrms with addition of a supplemental transformer.

Highly Survivable

Whether protecting a single floor or a an entire campus building, FxIP modules will continue to process local events in the event of a network communication failure. In addition, because of it’s isolation, the module will never go down for routine system maintenance in other sections of the system.

The DAPB-100 is designed to work with any manufacturer’s voice evacuation control panel including the VECP series. Each DAPB-100 also provides an additional four Class A or Class B 25 Vrms supervised speaker circuits with an option for 70 Vrms with addition of a supplemental transformer.

  • DAPB-100
  • SIG-3-REL
  • SIG-70V-XFMR

Inputs
Activation Voltage                     Polarity Reversal, Supervised, 9-30Vdc or Contact Closure, Supervised, 10K EOLR
Audio                                        25 Vrms Speaker Circuit
25K Impedance, 0.025 W loading
or
70 Vrms Speaker Circuit
70K Impedance, 0.07 W loading

Outputs
Audio                                         100 W; 25 Vrms (70 Vrms Optional)
Speaker circuits                          1; power-limited to 60 W
3; power-limited to 25 W each with total power not exceeding 100 W
10 K Ohm EOLR continuously monitored
Indicators
LED                                             power (green)
active (red)
system fault (yellow)
LED bar graph                            audio level; yellow 4-segment

Power Supply
Primary Power                            120 Vac, 60 Hz; 5 A nominal
Internal Power Supply                 24 Vdc regulated
External Power Supply                 24 Vdc regulated; Listed for Fire Alarm Use

Battery Backup – Standby Power
Use 24 Vdc, 10 AH battery for 24 hour normal operation and 15 minute operation in alarm with loss of primary AC power
Use larger capacity battery for longer operation with loss of primary AC power

DAPB-100 is extremely easy to add to a new or existing fire alarm/voice evacuation system and interfaces directly with both the voice evacuation control panel and any addressable or conventional FACP as needed. The DABP-100 has its own power supply with built-in battery charger. The audio input is provided by connection to an existing 25 Vrms or 70 Vrms speaker circuit. For activation, the DAPB-100 connects to a standard reverse polarity NAC circuit and/or a supervised dry contact trigger.

About

The DAPB-100 is designed to work with any manufacturer’s voice evacuation control panel including the VECP series. Each DAPB-100 also provides an additional four Class A or Class B 25 Vrms supervised speaker circuits with an option for 70 Vrms with addition of a supplemental transformer.

  • DAPB-100
  • SIG-3-REL
  • SIG-70V-XFMR
Data Sheet
Specs

Inputs
Activation Voltage                     Polarity Reversal, Supervised, 9-30Vdc or Contact Closure, Supervised, 10K EOLR
Audio                                        25 Vrms Speaker Circuit
25K Impedance, 0.025 W loading
or
70 Vrms Speaker Circuit
70K Impedance, 0.07 W loading

Outputs
Audio                                         100 W; 25 Vrms (70 Vrms Optional)
Speaker circuits                          1; power-limited to 60 W
3; power-limited to 25 W each with total power not exceeding 100 W
10 K Ohm EOLR continuously monitored
Indicators
LED                                             power (green)
active (red)
system fault (yellow)
LED bar graph                            audio level; yellow 4-segment

Power Supply
Primary Power                            120 Vac, 60 Hz; 5 A nominal
Internal Power Supply                 24 Vdc regulated
External Power Supply                 24 Vdc regulated; Listed for Fire Alarm Use

Battery Backup – Standby Power
Use 24 Vdc, 10 AH battery for 24 hour normal operation and 15 minute operation in alarm with loss of primary AC power
Use larger capacity battery for longer operation with loss of primary AC power

Architects

DAPB-100 is extremely easy to add to a new or existing fire alarm/voice evacuation system and interfaces directly with both the voice evacuation control panel and any addressable or conventional FACP as needed. The DABP-100 has its own power supply with built-in battery charger. The audio input is provided by connection to an existing 25 Vrms or 70 Vrms speaker circuit. For activation, the DAPB-100 connects to a standard reverse polarity NAC circuit and/or a supervised dry contact trigger.